U90 Ladder Software Manual
36
Analog output values are contained in the register that you link to the output in Hardware
Configuration.
Model number Resolution Range
V200-18-E1 (Snap-in I/O
module)
V120-12-R1, V120-12-R2C
M90 controllers (analog input)
M91-19-R1, M91-19-R2, R2C
10 bit (0-10V, 0-
20mA,
4-20mA)
0-1023, 1024 units (except at 4-
20mA)
204 to 1024, 820 units (at 4-
20mA)
V120-12-UN2
M90-19-UN2
M91-19-TC2
14 bit (0-10V, 4-
20mA)
Temperature ranges
appear in the
following table
0-16383, 16384 units (except at
4-20mA)
3277-16383, 13107 units (at 4-
20mA)
IO-AI4-AO2 Input
Output
12 bit (0-10V, 0-
20mA,
4-20mA)
12 bit +sign (±10V,
0-20mA,
4-20mA)
0-4095, 4096 units (except at4-
20mA)
819 to 4095, 3277 units (at 4-
20mA)
0-+4095(except at4-20mA)
819 to 4095, 3277 units (at 4-
20mA)
Model
number
Type Input ranges Range
V120-12-
UN2
M90-19-
UN2
M91-19-
TC2
mV
B
E
J
K
N
R
S
T
-5 to 56mV
200 to 1820°C (300 to
3276°F)
-200 to 750°C (-328 to
1382°F)
-200 to 760°C (-328 to
1400°F)
-200 to 1250°C (-328 to
2282°F)
-200 to 1300°C (-328 to
2372°F)
-0 to 1768°C (-32 to
3214°F)
-0 to 1768°C (-32 to
3214°F)
-200 to 400°C (-328 to
752°F)
-50 to 506°C
2000 to 18200°C (3000 to 32760°F)
-2000 to 7500°C (-3280 to 13820°F)
-2000 to 7600°C (-3280 to 14000°F)
-2000 to 12500°C (-3280 to 22820°F)
-2000 to 13000°C (-3280 to 23720°F)
-0 to 17680°C (-32 to 32140F)
-0 to 17680°C (-32 to 32140°F)
-200 to 4000°C (-3280 to 7520°F
IO-PT4 -50° to 460°C
-500° to 4600°C
Configuring a Thermocouple: M91 OPLC series